RXYQ30BYM
VRV 6H Series
Enables cooling and heating operation with a single VRV system.
- New large-capacity single module up to 24HP reduces installation space
- Significant energy savings with improved technology
- New reinforced design improves resistance to earthquakes and wind while protecting against falling damage.
- New High Efficiency Compressor loaded
- VRT Smart II control further improves energy saving
- Height difference extension Max. 110m
- Equivalent length extension Max. 190m
- Automatic refrigerant charge function
- Electrical component service window on the front panel
- Stable operation even in high outdoor temperatures up to 52CDB
Category
Technical Specifications
General | |
---|---|
Model | RXYQ30BYM |
Combination Unit 1 | RXYQ18BYM |
Combination Unit 2 | RXYQ12BYM |
Cooling Capacity (kW) | 83.500 |
Heating Capacity (kW) | 93.500 |
Power Input (Cooling) (kW) | 23.000 |
Power Input (Heating) (kW) | 24.600 |
Mechanicals | |
Compressor Type | Hermetically Sealed Scroll Type |
Heat Exchanger Type | Cross Fin Coil |
Unit Mass Weight (kg) | 565.000 |
Fan | |
Fan Type | Propeller Fan |
Fan Drive | Direct Drive |
Airflow Rate (CMH) | 26340.00 |
Maximum External Static Pressure (Pa) | 78.40 |
Electricals_50Hz | |
Power Supply_Voltage (V) | 400 |
Power Supply_Voltage range (V) | 380-415 |
Power Supply_Phase | 3 |
Power Supply_Frequency (Hz) | 50 |
Minimum Circuit Amps. (A) | 58.20 |
Maximum Fuse Amps. (A) | 70.0 |
Electricals_60Hz | |
Power Supply_Voltage (V) | 380 |
Power Supply_Voltage range (V) | 380 |
Power Supply_Phase | 3 |
Power Supply_Frequency (Hz) | 60 |
Minimum Circuit Amps. (A) | 53.80 |
Maximum Fuse Amps. (A) | 70.0 |
Dimensions | |
Height (mm) | 1660.0 |
Width (mm) | 2190.0 |
Depth (mm) | 765.0 |
Refrigerant | |
Refrigerant Type | R410A |
Refrigerant Base Charge (kg) | 18.900 |
Sound Level | |
Sound Pressure Level (dBA) | 64 |
Sound Power Level (dB) | 87 |
+Read more
Series
RXYQ-BYM_double
-
The item has been added
to your cart.
Other Series
RXYQ-BYM_single
-
The item has been added
to your cart.
RXYQ-BYM_triple
-
The item has been added
to your cart.
Other models in the same series (11 models)
Model Name | Nominal Cooling Capacity (kW) | Nominal Heating Capacity (kW) | |
---|---|---|---|
RXYQ26BYM | 73.500 | 82.500 |
The item has been added |
RXYQ28BYM | 78.500 | 87.500 |
The item has been added |
RXYQ32BYM | 89.500 | 100.000 |
The item has been added |
RXYQ34BYM | 96.000 | 108.000 |
The item has been added |
RXYQ36BYM | 101.000 | 113.000 |
The item has been added |
RXYQ38BYM | 106.000 | 119.000 |
The item has been added |
RXYQ40BYM | 112.000 | 126.000 |
The item has been added |
RXYQ42BYM | 117.000 | 132.000 |
The item has been added |
RXYQ44BYM | 123.000 | 138.000 |
The item has been added |
RXYQ46BYM | 128.000 | 144.000 |
The item has been added |